Reference

EU loss limits for distribution transformers

The Tier 2 load and no load loss ceilings that three phase medium power transformers must meet, as set out in Regulation (EU) No 548/2014 as amended.

Cast resin dry type transformer with red resin encapsulated coils on a blue frame, installed indoors with cables entering from above
Regulation
(EU) No 548/2014as amended by (EU) 2019/1783
Tier 2 applies from
1 July 2021
Tables
I.1 liquid immersed, I.2 dry typeAnnex I
Scope of the tables
one winding up to Um 24 kVand the other up to Um 3.6 kV
Ratings between rows
linear interpolationthe regulation's own rule
Great Britain
still appliedas EU derived legislation

These tables set the legal ceiling, not a manufacturer's value. A transformer in scope declares its own losses on its datasheet, at or below the ceiling for its rating and construction. Two units of the same rating from different manufacturers can declare different values below the same ceiling.

The tables apply to three phase medium power transformers with one winding at a highest voltage for equipment, Um, up to 24 kV and the other up to 3.6 kV. That covers the common 10, 11, 20 and 22 kV distribution systems with a low voltage secondary. A rating between two rows is found by linear interpolation, as footnote 1 to each table requires.

Table I.1, liquid immersed, Tier 2

Rated powerMaximum load losses PkMaximum no load losses P0Class
≤ 25 kVA600 W63 WAk, Ao − 10 %
50 kVA750 W81 WAk, Ao − 10 %
100 kVA1,250 W130 WAk, Ao − 10 %
160 kVA1,750 W189 WAk, Ao − 10 %
250 kVA2,350 W270 WAk, Ao − 10 %
315 kVA2,800 W324 WAk, Ao − 10 %
400 kVA3,250 W387 WAk, Ao − 10 %
500 kVA3,900 W459 WAk, Ao − 10 %
630 kVA4,600 W540 WAk, Ao − 10 %
800 kVA6,000 W585 WAk, Ao − 10 %
1000 kVA7,600 W693 WAk, Ao − 10 %
1250 kVA9,500 W855 WAk, Ao − 10 %
1600 kVA12,000 W1,080 WAk, Ao − 10 %
2000 kVA15,000 W1,305 WAk, Ao − 10 %
2500 kVA18,500 W1,575 WAk, Ao − 10 %
3150 kVA23,000 W1,980 WAk, Ao − 10 %

The first row applies to ratings up to and including 25 kVA.

Table I.2, dry type, Tier 2

Rated powerMaximum load losses PkMaximum no load losses P0Class
≤ 50 kVA1,500 W180 WAk, Ao − 10 %
100 kVA1,800 W252 WAk, Ao − 10 %
160 kVA2,600 W360 WAk, Ao − 10 %
250 kVA3,400 W468 WAk, Ao − 10 %
400 kVA4,500 W675 WAk, Ao − 10 %
630 kVA7,100 W990 WAk, Ao − 10 %
800 kVA8,000 W1,170 WAk, Ao − 10 %
1000 kVA9,000 W1,395 WAk, Ao − 10 %
1250 kVA11,000 W1,620 WAk, Ao − 10 %
1600 kVA13,000 W1,980 WAk, Ao − 10 %
2000 kVA16,000 W2,340 WAk, Ao − 10 %
2500 kVA19,000 W2,790 WAk, Ao − 10 %
3150 kVA22,000 W3,420 WAk, Ao − 10 %

The first row applies to ratings up to and including 50 kVA. The table has no 315 kVA or 500 kVA row, so those ratings are interpolated.

Where the tables are corrected or replaced

CaseWhat the regulation does
Primary at Um 36 kV, for example 33 kV systemsApplies correction factors from Table I.3a to the load and no load ceilings
Secondary above Um 3.6 kVApplies correction factors from Table I.3a
Dual voltage windings differing by more than 10 %Applies correction factors from Table I.3b, depending on how the dual voltage is rated
Liquid immersed pole mounted transformersUses its own table, Table I.6
Ratings above 3 150 kVASets a minimum Peak Efficiency Index instead of absolute ceilings

Each correction factor depends on the exact configuration, so it is read from Table I.3a or I.3b for the case in hand.

Worked interpolation

RatingConstructionBetween rowsLoad losses PkNo load losses P0
200 kVALiquid immersed160 and 250 kVA2,017 W225 W
500 kVADry type400 and 630 kVA5,630 W812 W
315 kVADry type250 and 400 kVA3,877 W558 W

Linear interpolation between the adjacent table rows, rounded to the nearest watt.

What the regulation excludes

The regulation lists applications it does not cover, including instrument transformers and transformers specifically designed to provide a DC supply to electronic or rectifier loads. That exemption expressly does not extend to transformers intended to provide an AC supply from DC sources, such as those for wind turbine and photovoltaic applications. Those stay in scope.

Sources

SourceWhat was read
EUR-Lex, consolidated text CELEX 02014R0548-20191114Annex I, Tables I.1 to I.6, footnotes, and the scope exclusions
legislation.gov.ukThe same Tier 2 values for 630 to 2500 kVA, and the regulation's continued application in Great Britain

Read on 16 September 2026. Commission Regulation (EU) No 548/2014 as amended by (EU) 2019/1783.

How to cite

Cite as

Daverlan Power Systems (2026). EU loss limits for distribution transformers. https://daverlan.com/technical-resources/transformer-loss-limits/

Licence

Creative Commons Attribution 4.0 International, CC BY 4.0

The data may be reused, redistributed and built on, including commercially, provided the source is credited.

Permanent address

https://daverlan.com/technical-resources/transformer-loss-limits/

This address does not change. Where the figures are revised the page is versioned and the address stays as it is.