Reference
EU loss limits for distribution transformers
The Tier 2 load and no load loss ceilings that three phase medium power transformers must meet, as set out in Regulation (EU) No 548/2014 as amended.

- Regulation
- (EU) No 548/2014as amended by (EU) 2019/1783
- Tier 2 applies from
- 1 July 2021
- Tables
- I.1 liquid immersed, I.2 dry typeAnnex I
- Scope of the tables
- one winding up to Um 24 kVand the other up to Um 3.6 kV
- Ratings between rows
- linear interpolationthe regulation's own rule
- Great Britain
- still appliedas EU derived legislation
These tables set the legal ceiling, not a manufacturer's value. A transformer in scope declares its own losses on its datasheet, at or below the ceiling for its rating and construction. Two units of the same rating from different manufacturers can declare different values below the same ceiling.
The tables apply to three phase medium power transformers with one winding at a highest voltage for equipment, Um, up to 24 kV and the other up to 3.6 kV. That covers the common 10, 11, 20 and 22 kV distribution systems with a low voltage secondary. A rating between two rows is found by linear interpolation, as footnote 1 to each table requires.
Table I.1, liquid immersed, Tier 2
| Rated power | Maximum load losses Pk | Maximum no load losses P0 | Class |
|---|---|---|---|
| ≤ 25 kVA | 600 W | 63 W | Ak, Ao − 10 % |
| 50 kVA | 750 W | 81 W | Ak, Ao − 10 % |
| 100 kVA | 1,250 W | 130 W | Ak, Ao − 10 % |
| 160 kVA | 1,750 W | 189 W | Ak, Ao − 10 % |
| 250 kVA | 2,350 W | 270 W | Ak, Ao − 10 % |
| 315 kVA | 2,800 W | 324 W | Ak, Ao − 10 % |
| 400 kVA | 3,250 W | 387 W | Ak, Ao − 10 % |
| 500 kVA | 3,900 W | 459 W | Ak, Ao − 10 % |
| 630 kVA | 4,600 W | 540 W | Ak, Ao − 10 % |
| 800 kVA | 6,000 W | 585 W | Ak, Ao − 10 % |
| 1000 kVA | 7,600 W | 693 W | Ak, Ao − 10 % |
| 1250 kVA | 9,500 W | 855 W | Ak, Ao − 10 % |
| 1600 kVA | 12,000 W | 1,080 W | Ak, Ao − 10 % |
| 2000 kVA | 15,000 W | 1,305 W | Ak, Ao − 10 % |
| 2500 kVA | 18,500 W | 1,575 W | Ak, Ao − 10 % |
| 3150 kVA | 23,000 W | 1,980 W | Ak, Ao − 10 % |
The first row applies to ratings up to and including 25 kVA.
Table I.2, dry type, Tier 2
| Rated power | Maximum load losses Pk | Maximum no load losses P0 | Class |
|---|---|---|---|
| ≤ 50 kVA | 1,500 W | 180 W | Ak, Ao − 10 % |
| 100 kVA | 1,800 W | 252 W | Ak, Ao − 10 % |
| 160 kVA | 2,600 W | 360 W | Ak, Ao − 10 % |
| 250 kVA | 3,400 W | 468 W | Ak, Ao − 10 % |
| 400 kVA | 4,500 W | 675 W | Ak, Ao − 10 % |
| 630 kVA | 7,100 W | 990 W | Ak, Ao − 10 % |
| 800 kVA | 8,000 W | 1,170 W | Ak, Ao − 10 % |
| 1000 kVA | 9,000 W | 1,395 W | Ak, Ao − 10 % |
| 1250 kVA | 11,000 W | 1,620 W | Ak, Ao − 10 % |
| 1600 kVA | 13,000 W | 1,980 W | Ak, Ao − 10 % |
| 2000 kVA | 16,000 W | 2,340 W | Ak, Ao − 10 % |
| 2500 kVA | 19,000 W | 2,790 W | Ak, Ao − 10 % |
| 3150 kVA | 22,000 W | 3,420 W | Ak, Ao − 10 % |
The first row applies to ratings up to and including 50 kVA. The table has no 315 kVA or 500 kVA row, so those ratings are interpolated.
Where the tables are corrected or replaced
| Case | What the regulation does |
|---|---|
| Primary at Um 36 kV, for example 33 kV systems | Applies correction factors from Table I.3a to the load and no load ceilings |
| Secondary above Um 3.6 kV | Applies correction factors from Table I.3a |
| Dual voltage windings differing by more than 10 % | Applies correction factors from Table I.3b, depending on how the dual voltage is rated |
| Liquid immersed pole mounted transformers | Uses its own table, Table I.6 |
| Ratings above 3 150 kVA | Sets a minimum Peak Efficiency Index instead of absolute ceilings |
Each correction factor depends on the exact configuration, so it is read from Table I.3a or I.3b for the case in hand.
Worked interpolation
| Rating | Construction | Between rows | Load losses Pk | No load losses P0 |
|---|---|---|---|---|
| 200 kVA | Liquid immersed | 160 and 250 kVA | 2,017 W | 225 W |
| 500 kVA | Dry type | 400 and 630 kVA | 5,630 W | 812 W |
| 315 kVA | Dry type | 250 and 400 kVA | 3,877 W | 558 W |
Linear interpolation between the adjacent table rows, rounded to the nearest watt.
What the regulation excludes
The regulation lists applications it does not cover, including instrument transformers and transformers specifically designed to provide a DC supply to electronic or rectifier loads. That exemption expressly does not extend to transformers intended to provide an AC supply from DC sources, such as those for wind turbine and photovoltaic applications. Those stay in scope.
Sources
| Source | What was read |
|---|---|
| EUR-Lex, consolidated text CELEX 02014R0548-20191114 | Annex I, Tables I.1 to I.6, footnotes, and the scope exclusions |
| legislation.gov.uk | The same Tier 2 values for 630 to 2500 kVA, and the regulation's continued application in Great Britain |
Read on 16 September 2026. Commission Regulation (EU) No 548/2014 as amended by (EU) 2019/1783.
How to cite
- Cite as
Daverlan Power Systems (2026). EU loss limits for distribution transformers. https://daverlan.com/technical-resources/transformer-loss-limits/
- Licence
Creative Commons Attribution 4.0 International, CC BY 4.0
The data may be reused, redistributed and built on, including commercially, provided the source is credited.
- Permanent address
https://daverlan.com/technical-resources/transformer-loss-limits/
This address does not change. Where the figures are revised the page is versioned and the address stays as it is.