Data centre

Busbar trunking and busway

Busbar trunking, called busway in the US, runs over rack rows with plug in tap off units and in risers and transformer links, specified by current, conductor and route.

Rated current
A, per run
Conductor
copper or aluminium
Use
rack rows, riser, transformer link
Tap offs
number and ratingfor rack rows
Standard
IEC 61439-6busbar trunking systems

Over a rack row, busway replaces a run of cables with one track and plug in tap off units, so a rack can be powered or moved without a shutdown. In a riser or between a transformer and its main switchboard, busbar trunking carries currents that would take many parallel cables.

The route is the specification: straight lengths, elbows, the feed unit and every tap off with its rating and protection.

What gets specified

ParameterTypical optionsWhat decides it
Rated current160 A to 6300 AThe load per run
ConductorCopper or aluminiumWeight, size and cost
Voltage and system400 V, 3 phase with neutral and earthThe board it is fed from
Degree of protectionIP54 or IP55 for risers; lower for overhead runsThe space it runs through
Tap off unitsNumber, rating, protection, meteringThe racks or loads served
Short circuit ratingkA for a stated durationThe fault level

A busway run

Feed unitBuswayTap offRack PDUTap offRack PDUTap offRack PDUTap offRack PDUTap offRack PDUOverhead busway with tap off units, schematic
Schematic. One feed unit, the busway over the row and a plug in tap off unit for each rack or pair of racks.

Applicable standards

StandardWhat it covers
IEC 61439-6Low voltage switchgear and controlgear assemblies, busbar trunking systems
BS EN 61439-6:2012The current GB edition, Busbar trunking systems (busways), designated by BSI; a revised edition exists only in draft
BS 8519:2020Fire resistant power and control cable systems for life safety and fire fighting, code of practice

Fire rules in a UK building

Since the 18th edition, regulation 521.10.202 of BS 7671 requires wiring systems throughout an installation to be supported so they will not collapse early in a fire; the IET gives the purpose as keeping hanging wiring from hindering evacuation and firefighters. BEAMA's guide reads the BS 7671 definition of a wiring system as including busbars, so a busway's hangers are part of that question.

Where a run feeds life safety or fire fighting equipment, BS 8519:2020 is the code of practice for fire resistant power and control cable systems. BSI's description does not say whether it covers busbar systems, so ask the maker for evidence of fire integrity for the system offered. Where the run passes through a fire separating wall or floor, Approved Document B asks for the opening to be fire stopped.

What we need to quote

  1. Use: rack rows, riser or transformer link
  2. Rated current and voltage
  3. Route with lengths, elbows and the feed point
  4. Number and rating of tap off units, and their protection
  5. Fault level and degree of protection
  6. Destination and the date required on site