Automatic transfer switches and ATS panels

An automatic transfer switch moves the load between mains and a generator, or between two sources, and is specified by current, poles, transition and the load it switches.

Rated current
A, at the switched voltage
Poles
3, or 4 with switched neutralset by the earthing system
Transition
open, delayed or closedset by the load and the operator
Utilisation category
for example AC-33BIEC 60947-6-1
Short circuit withstand
kA, with the protecting device

A transfer switch decides how the load sees an outage. In open transition it breaks from one source before it makes onto the other; a delayed transition adds a pause so motors and transformers lose their residual voltage first. In closed transition the two sources are paralleled for a moment, which needs synchronising and often the network operator's consent.

Whether the neutral is switched follows from the earthing of the generator. Where the set's neutral is earthed at the set, a four pole switch keeps the two earthing points apart and stops neutral current from splitting between paths.

MainsGeneratorTransfer switchLoad
Schematic. The switch connects the load to the mains or to the generator, never to both in open transition.

Changeover on a GB distribution network

No one may run generation in parallel with a public network without the distribution network operator's agreement, a rule Engineering Recommendation G99 takes from regulation 22 of the ESQCR. G99 Issue 2, of 10 March 2025, sorts standby sets into operating modes, and the mode decides what the transfer equipment must do.

In short term parallel operation, mode OM3, the set may run in parallel for at most five minutes in any month and no more than once a week. Beyond that it counts as long term parallel, unless the operator agrees otherwise. OM3 needs a parallel time interlock separate from the changeover control and under and over voltage and frequency protection, but no loss of mains relay.

In a changeover with no parallel at all, mode OM4, the interlocking must be fail safe, the changeover may not rely on removable fuses, and the set needs an independent earth electrode. The operator may inspect the installation and witness its commissioning.

Break classes for safety services, BS 7671

ClassChangeover within
No breakcontinuous supply
Very short break0.15 s
Short break0.5 s
Medium break15 s
Long breakmore than 15 s

BS 7671 regulation 560.4.1, as set out in IET Guidance Note 7. A set started on mains failure reaches the medium break class and no shorter, so loads that need a shorter break sit behind a UPS.

What gets specified

ParameterTypical optionsWhat decides it
Rated current125 A to 4000 AThe load and the busbar it feeds
Poles3 or 4The earthing system of both sources
TransitionOpen, delayed, closedMotor loads, UPS input and the operator
SourcesMains and generator, generator and generator, two mainsThe supply arrangement
Utilisation categoryAC-31B, AC-32B, AC-33BResistive, mixed or motor loads
Short circuit withstandkA with the upstream protectionThe fault level at the switch
ControlsMains sensing, test, exercise, remote signallingThe site's control system

Applicable standard

StandardWhat it covers
IEC 60947-6-1Low voltage transfer switching equipment

The quotation confirms the edition and the utilisation category the switch is tested to.

What we need to quote

  1. Rated current and voltage
  2. 3 or 4 poles, and the earthing system of both sources
  3. Open, delayed or closed transition
  4. The loads switched, or the utilisation category from the specification
  5. Fault level at the switch and the upstream protection
  6. The G99 operating mode agreed with the network operator: no parallel, or short term parallel
  7. Enclosure, and how the controls report to the site