Substations

Package substations

A ring main unit, a transformer and a low voltage cabinet close coupled on a common base, installed outdoors without a separate building.

Prefabricated compact substation in a light concrete enclosure with dark ventilated doors, set on site with red cable ducts in the foreground
Arrangement
close coupled on a common baseno connecting cables between units
Placement
outdoors on a plintheach unit carries its own weather protection
Medium voltage
ring main unitconfiguration set by the network
Transformer
liquid immersed, commonly
Low voltage
cabinet with incomer and outgoing waysset by the loads

A package substation joins the ring main unit, the transformer and the low voltage cabinet directly to one another on a common base. Close coupling removes the interconnecting cables and the building from the site works. What remains is the foundation, the incoming and outgoing cables and the earthing.

With no building, each unit relies on its own enclosure for weather protection, and the arrangement is more exposed than a prefabricated station. Where security, appearance or climate call for an enclosure, a compact substation or a separate housing is the usual alternative.

In Great Britain, a package substation owned by a distributor or generator falls under regulation 11 of the ESQCR. Live equipment in the open air is fenced or walled to at least 2.4 m, and the station carries safety signs and a notice naming its location, its owner or operator and a constantly attended telephone number.

What gets specified

ParameterTypical optionsWhat decides it
Ring main unitConfiguration and insulation mediumThe network, and the rules on fluorinated gas at the destination
TransformerLiquid immersed in most packages, flanged to the units either sideThe load, and the flange arrangement of the switchgear chosen
Low voltage cabinetIncomer and fused outgoing waysThe circuits the site needs
Base and couplingCommon skid or plinth, flange coupling between unitsThe manufacturer's arrangement
Weather protectionThe IP rating of each unit's own enclosureExposure at the installed position
SurroundNone, or a fence or housingSecurity, appearance and climate

Applicable standards

StandardWhat it covers
IEC 62271-200The ring main unit at one end of the package
IEC 60076-1The transformer in the middle
IEC 61439-1 and IEC 61439-2The low voltage cabinet at the other end
IEC 60529The IP code each unit's own enclosure is rated to

What a package substation request needs

  1. The ring main unit configuration and its insulation medium
  2. The transformer rating and voltage pair
  3. The low voltage incomer and the number of fused ways
  4. Whether a surround or housing is wanted
  5. The plinth dimensions, where the plinth already exists

Specification template

Fill it in on screen or by hand, then upload it with your request.

Request offers for this equipment