Reference
Transformer sizing guide, from load to rating
A working method from connected load to a standard rating, and the two factors that most often make a first estimate wrong.

Start from the connected load, then apply diversity, because connected load and simultaneous load are rarely the same number. A workshop with forty machines does not run all forty at once. Size for forty and the transformer comes out larger and more expensive than the site needs, and less efficient at the load it carries.
Divided by the power factor, the simultaneous load gives a demand in kilovolt amperes. The rating is built up from there.
The two factors that change the answer
Motor starting is the first. A motor started direct on line draws several times its rated current while it accelerates, and the rest of the installation feels the voltage dip.
Where a large motor starts on a small transformer, that dip sets the rating. Soft starters and variable speed drives reduce it considerably, so the starting method belongs in the calculation.
Power factor is the second. Ratings are stated in kilovolt amperes, loads are often given in kilowatts, and the two differ by the power factor. Converting a kilowatt figure without it understates the rating.
Six steps from load to rating
| Step | Produces |
|---|---|
| Sum the connected load | Connected kW |
| Apply a diversity factor per load group | Simultaneous kW |
| Divide by power factor | Demand in kVA |
| Check the largest motor start against the candidate rating | A voltage dip figure |
| Add growth that is already planned | Design demand |
| Round up to the next standard rating | The rating to specify |
kW to kVA for four loads
| Load | Power factor | Demand | Next standard rating |
|---|---|---|---|
| 100 kW | 0.80 | 125 kVA | 160 kVA |
| 100 kW | 0.90 | 111 kVA | 160 kVA |
| 100 kW | 0.95 | 105 kVA | 160 kVA |
| 200 kW | 0.80 | 250 kVA | 250 kVA |
| 200 kW | 0.90 | 222 kVA | 250 kVA |
| 200 kW | 0.95 | 211 kVA | 250 kVA |
| 500 kW | 0.80 | 625 kVA | 630 kVA |
| 500 kW | 0.90 | 556 kVA | 630 kVA |
| 500 kW | 0.95 | 526 kVA | 630 kVA |
| 1000 kW | 0.80 | 1,250 kVA | 1250 kVA |
| 1000 kW | 0.90 | 1,111 kVA | 1250 kVA |
| 1000 kW | 0.95 | 1,053 kVA | 1250 kVA |
Demand = kW ÷ power factor, rounded, then the next step of the common series 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA. These rows are the arithmetic alone; diversity, growth, harmonics, derating and motor starting all come before a rating is chosen. A "200 kW transformer" is a transformer that can carry a 200 kW load, and its rating is in kVA.
Where the engineer decides
The method gives a rating you can defend and a specification a manufacturer can quote. Where the load is unusual, carries harmonics or feeds a critical supply, the final rating belongs to the engineer who signs the design.
How to cite
- Cite as
Daverlan Power Systems (2026). Transformer sizing guide, from load to rating. https://daverlan.com/technical-resources/transformer-sizing/
- Permanent address
https://daverlan.com/technical-resources/transformer-sizing/
This address does not change. Where the figures are revised the page is versioned and the address stays as it is.