Reference
How a transformer rating is decided
A working method for arriving at a rating, and the two factors that most often make a first estimate wrong.
Start from the connected load, then apply diversity, because connected load and simultaneous load are rarely the same number. A workshop with forty machines does not run forty machines at once, and a rating built on the assumption that it does will be larger, more expensive and less efficient than the one the site needs.
The result of that step is a demand in kilovolt amperes. It is the starting point rather than the answer.
The two factors that change the answer
Motor starting is the first. A direct on line motor draws several times its rated current while it accelerates, and the resulting voltage dip is what the rest of the installation notices. Where a large motor starts against a small transformer, the rating is decided by the dip rather than by the running load. Soft starters and variable speed drives change this materially, so how a motor starts belongs in the calculation.
Power factor is the second. Ratings are stated in kilovolt amperes and loads are frequently described in kilowatts, and the two differ by the power factor. Converting a kilowatt figure without it understates the rating.
A working sequence
| Step | Produces |
|---|---|
| Sum the connected load | Connected kW |
| Apply a diversity factor per load group | Simultaneous kW |
| Divide by power factor | Demand in kVA |
| Check the largest motor start against the candidate rating | A voltage dip figure |
| Add planned growth, not speculative growth | Design demand |
| Round up to the next standard rating | The rating to specify |
From kW to kVA, worked for four loads
| Load | Power factor | Demand | Next standard rating |
|---|---|---|---|
| 100 kW | 0.80 | 125 kVA | 160 kVA |
| 100 kW | 0.90 | 111 kVA | 160 kVA |
| 100 kW | 0.95 | 105 kVA | 160 kVA |
| 200 kW | 0.80 | 250 kVA | 250 kVA |
| 200 kW | 0.90 | 222 kVA | 250 kVA |
| 200 kW | 0.95 | 211 kVA | 250 kVA |
| 500 kW | 0.80 | 625 kVA | 630 kVA |
| 500 kW | 0.90 | 556 kVA | 630 kVA |
| 500 kW | 0.95 | 526 kVA | 630 kVA |
| 1000 kW | 0.80 | 1,250 kVA | 1250 kVA |
| 1000 kW | 0.90 | 1,111 kVA | 1250 kVA |
| 1000 kW | 0.95 | 1,053 kVA | 1250 kVA |
Demand = kW ÷ power factor, rounded, then the next step of the common series 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA. The arithmetic only: diversity, growth, harmonics, derating and motor starting come before a rating is chosen. A request for a "200 kW transformer" is a request for a transformer that can carry a 200 kW load, and transformers are rated in kVA.
Where this ends
This method gets a project to a rating that is defensible and to a specification that a supplier can price. It does not replace the design a qualified engineer signs, and the final rating on a project with unusual load behaviour, harmonics or a critical supply belongs to that engineer.
Cite this page
- Cite as
Daverlan Power Systems (2026). How a transformer rating is decided. https://daverlan.com/technical-resources/transformer-sizing/
- Permanent address
https://daverlan.com/technical-resources/transformer-sizing/
This address does not change. Where the figures are revised the page is versioned and the address stays as it is.