Reference

Transformer sizing guide, from load to rating

A working method from connected load to a standard rating, and the two factors that most often make a first estimate wrong.

Outdoor power transformer with high and low voltage bushings, surge arresters and a radiator bank against a blue sky

Start from the connected load, then apply diversity, because connected load and simultaneous load are rarely the same number. A workshop with forty machines does not run all forty at once. Size for forty and the transformer comes out larger and more expensive than the site needs, and less efficient at the load it carries.

Divided by the power factor, the simultaneous load gives a demand in kilovolt amperes. The rating is built up from there.

The two factors that change the answer

Motor starting is the first. A motor started direct on line draws several times its rated current while it accelerates, and the rest of the installation feels the voltage dip.

Where a large motor starts on a small transformer, that dip sets the rating. Soft starters and variable speed drives reduce it considerably, so the starting method belongs in the calculation.

Power factor is the second. Ratings are stated in kilovolt amperes, loads are often given in kilowatts, and the two differ by the power factor. Converting a kilowatt figure without it understates the rating.

Six steps from load to rating

StepProduces
Sum the connected loadConnected kW
Apply a diversity factor per load groupSimultaneous kW
Divide by power factorDemand in kVA
Check the largest motor start against the candidate ratingA voltage dip figure
Add growth that is already plannedDesign demand
Round up to the next standard ratingThe rating to specify

kW to kVA for four loads

LoadPower factorDemandNext standard rating
100 kW0.80125 kVA160 kVA
100 kW0.90111 kVA160 kVA
100 kW0.95105 kVA160 kVA
200 kW0.80250 kVA250 kVA
200 kW0.90222 kVA250 kVA
200 kW0.95211 kVA250 kVA
500 kW0.80625 kVA630 kVA
500 kW0.90556 kVA630 kVA
500 kW0.95526 kVA630 kVA
1000 kW0.801,250 kVA1250 kVA
1000 kW0.901,111 kVA1250 kVA
1000 kW0.951,053 kVA1250 kVA

Demand = kW ÷ power factor, rounded, then the next step of the common series 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA. These rows are the arithmetic alone; diversity, growth, harmonics, derating and motor starting all come before a rating is chosen. A "200 kW transformer" is a transformer that can carry a 200 kW load, and its rating is in kVA.

Where the engineer decides

The method gives a rating you can defend and a specification a manufacturer can quote. Where the load is unusual, carries harmonics or feeds a critical supply, the final rating belongs to the engineer who signs the design.

How to cite

Cite as

Daverlan Power Systems (2026). Transformer sizing guide, from load to rating. https://daverlan.com/technical-resources/transformer-sizing/

Permanent address

https://daverlan.com/technical-resources/transformer-sizing/

This address does not change. Where the figures are revised the page is versioned and the address stays as it is.