Transformers

Power transformers

Power transformers are rated in MVA and engineered for each project, for primary substations, generation connections and large industrial supplies.

Outdoor power transformer with high and low voltage bushings, surge arresters and a radiator bank against a blue sky
Rating
in MVAset by the connection and the load or generation
Voltage regulation
commonly an on load tap changerset by the network voltage range
Cooling
ONAN, ONAF or forced oil stagesset by the load profile
Engineering
designed per projectno standard catalogue value applies
Standard
IEC 60076 seriesIEEE C57.12.00 on North American specifications

Power transformers sit above the distribution range. They connect transmission and subtransmission networks to distribution, connect generation to the grid and supply the largest industrial loads. Each is engineered to its project, so the specification carries more weight than for a distribution unit, and the documents exchanged before an order run longer.

Three questions settle feasibility early. The weight and dimensions of the main tank decide the route, and sometimes the site. An on load tap changer adds cost and maintenance, and lets the unit follow the network voltage. Factory acceptance tests are normally witnessed, so they go into the programme.

What gets specified

ParameterTypical optionsWhat decides it
RatingIn MVA, with cooling stage ratings where applicableThe connection, the load or the generation
Voltage ratioTransmission or subtransmission to distribution voltageThe networks on either side
Tap changerOn load or off circuit, with the tapping rangeThe voltage variation to be followed
CoolingONAN, ONAF, OFAF or equivalent stagesThe load cycle and the hottest ambient on site
ImpedanceSpecified per projectThe fault level and the parallel operation
Transport limitsMaximum shipping weight and dimensionsThe route to site
TestingRoutine, type and special tests, and witnessingThe specification and the owner's standard

Applicable standards

StandardWhat it covers
IEC 60076-1General requirements, with the project specification adding what a catalogue unit would not need
IEC 60076-7Loading guide, used when the owner wants ratings for cyclic or emergency loading
Regulation (EU) No 548/2014, as amendedAbove 3150 kVA the regulation sets a minimum Peak Efficiency Index rather than absolute loss ceilings
IEEE C57.12.00General requirements for liquid immersed power transformers on North American specifications

Documents normally exchanged

DocumentWhat it evidences
Technical specification and data scheduleThe owner's requirements, and the values the manufacturer declares against them
Outline and transport drawingsDimensions, shipping weight and the arrangement on site
Test planRoutine, type and special tests, and which are witnessed
Factory acceptance test reportResults of the tests carried out before dispatch
Transport and erection instructionsHandling, assembly and filling on site
Operating and maintenance manualOperation, the tap changer and maintenance intervals

What a power transformer request needs

  1. Rating in MVA and any cooling stage ratings
  2. Voltage ratio, vector group and impedance requirement
  3. Tap changer type and tapping range
  4. The standard and the owner's technical specification
  5. Site location and any known transport restriction
  6. Testing and witnessing requirements

Delivery and logistics

Power transformers normally travel as abnormal loads, often drained and with fittings removed, and are assembled, filled and tested on site. The route survey belongs in the project from the start, and the shipping weight of the main tank is one of the first values to fix.

Delivery dates follow manufacturer loading. Each quotation states the date for the unit offered.