Switchgear

Low voltage switchgear and LV switchboards

Main switchboards and power distribution assemblies up to 1000 V AC, sized from the rated current of the transformer that feeds them.

Standard
IEC 61439-1 and IEC 61439-2power switchgear assemblies up to 1000 V AC or 1500 V DC
Incomer
sized from the transformer currentcommonly 630 A to 6300 A
Devices
air and moulded case circuit breakersIEC 60947-2
Internal separation
Forms of separationset by the continuity of service required
Short circuit rating
kA for a stated durationset by the transformer and the upstream network

A main low voltage switchboard is sized from the transformer that feeds it. The transformer's rated current sets the incomer and the busbar. Its impedance and the upstream network set the prospective fault level, which the board must withstand and its breakers must interrupt.

The board is designed and verified to IEC 61439. The original manufacturer and the assembly manufacturer carry the verification of temperature rise, short circuit withstand and dielectric properties. The internal separation between busbars, functional units and terminals decides how much of the board stays energised while one part is worked on.

What gets specified

ParameterTypical optionsWhat decides it
Rated current of the incomer630 A to 6300 AThe transformer rated current
Rated short time withstand currentkA for a stated durationThe prospective fault level
Form of internal separationForm 1 to Form 4 as defined in IEC 61439-2The continuity of service required during maintenance
Incoming deviceAir circuit breaker or moulded case circuit breakerThe current and the protection functions needed
Outgoing waysNumber, ratings and device typesThe loads supplied
Busbar and connectionCable or busbar trunking from the transformerThe current and the room layout
Metering and monitoringMeters, power quality, communicationThe owner's energy management
Degree of protectionIP ratingThe room the board stands in

Applicable standards

StandardWhat it covers
IEC 61439-1The general rules, including how design verification is split between original and assembly manufacturer
IEC 61439-2The board as a power switchgear assembly, up to 1000 V AC or 1500 V DC, including the forms of separation
IEC 60947-2The air and moulded case circuit breakers it is built from
IEC 60529The IP code of the enclosure

Verification documents for an IEC 61439 board

DocumentWhat it proves
Design verification recordsTemperature rise, short circuit withstand and dielectric properties of the design, from the original manufacturer
Routine verification reportThe checks on the board as built, from the assembly manufacturer
Schedule of outgoing waysEach way's device, rating and setting as built

What a low voltage switchgear request needs

  1. Incomer rating, or the transformer rating and secondary voltage that feed the board
  2. Prospective fault level at the board, or the transformer impedance and upstream network data
  3. Form of internal separation required
  4. Schedule of outgoing ways with ratings and device types
  5. Connection from the transformer: cable or busbar trunking
  6. Metering, monitoring and communication requirements
  7. IP rating and the room dimensions

Questions buyers ask

What incomer rating does my transformer need?

Start from the transformer's rated current at the secondary voltage, 400 V or 433 V, then take the next standard device rating above it. The kVA to amps calculator gives that current from the rating and the voltage. Your designer confirms the choice against loading and discrimination.