Protection and control

Protection relays

Numerical relays that measure currents and voltages from instrument transformers and trip the breaker when the scheme's conditions are met.

Standard
IEC 60255 seriesmeasuring relays and protection equipment
Inputs
current and voltage transformersratios and classes set by the scheme
Functions
overcurrent, earth fault, differential and moreset by the protected equipment
Communication
protocol set by the substation system
Settings
applied at commissioningagreed with the network operator where required

A protection relay is specified by the equipment it protects and the scheme it sits in. A feeder relay commonly provides overcurrent and earth fault protection. A transformer relay adds differential protection, and a motor relay adds thermal and starting supervision.

Specifications often name the functions by their ANSI device numbers, for example 50 and 51 for overcurrent and 87 for differential protection.

The relay depends on what feeds it. The current and voltage transformer ratios and classes have to match, and so do the auxiliary supply voltage and the communication protocol of the substation system.

What gets specified

ParameterTypical optionsWhat decides it
Protected equipmentFeeder, transformer, motor, generator, busbarThe single line diagram
Protection functionsOvercurrent, earth fault, differential, voltage, frequencyThe protection scheme
Current and voltage inputs1 A or 5 A secondary, voltage inputsThe instrument transformers
Auxiliary supplyDC or AC voltageThe station battery or auxiliary system
CommunicationSubstation protocol and portsThe control system
MountingFlush panel mounting, cut out sizeThe panel, especially for replacements
Inputs and outputsNumber of binary inputs and output contactsInterlocking and alarm needs

Applicable standards

StandardWhat it covers
IEC 60255-1The common requirements for the relay as a product
IEC 60255-151Functional requirements for over and under current protection, the functions most feeder relays carry
IEC 61869-2The current transformers that feed the relay
IEC 61850Communication networks and systems for power utility automation, where the substation system uses it

What makes a relay usable on the day

ItemWhy it matters
Firmware version and settings file formatYour configuration tool has to read and write the relay
Communication configurationThe protocol and data model your station system expects
Cut out and terminal drawingA replacement has to fit the existing panel door and wiring

What a protection relay request needs

  1. The protected equipment, and the functions by name or ANSI number
  2. Current transformer secondary, 1 A or 5 A, and the voltage inputs
  3. The auxiliary supply voltage
  4. The station's communication protocol
  5. For a replacement: the old relay's model, firmware and cut out size

Questions buyers ask

Who calculates the protection settings?

Your protection engineer calculates them from the network study, and the party that commissions the scheme applies them. The relays we source carry the functions and interfaces that scheme needs.