Assemblies that switch, isolate and protect a distribution system, from the medium voltage connection down to the low voltage board.

Specified by

Rated voltage
the system it operates on
Rated current
busbar and each feederset by the loads and the transformers
Short time withstand
kA for a stated durationset by the fault level at the connection
Panel schedule
incomers, feeders, couplers, meteringthe specification itself
Insulation medium
air, gas or solidset by footprint and destination rules
Outline drawing for orientation.Not a photograph of a specific unit. Arrangement, enclosure and dimensions depend on the unit offered.

Switchgear is specified against the network rather than against the load. The rated voltage, the short time withstand current and the internal arc classification all come from the conditions at the connection point, so an assembly that is correct for one site can be unusable at the next.

The practical consequence is that the network operator's requirements and the fault level need to be in hand before an assembly is priced. Where they are not yet available we say so and quote against a stated assumption rather than an implied one.

Switchgear types

Insulating gas and the EU F gas rules

SwitchgearPutting into operation with fluorinated gas in the insulating or breaking medium is prohibited from
Medium voltage, primary and secondary distribution, up to and including 24 kV1 January 2026
Medium voltage, primary and secondary distribution, above 24 kV up to and including 52 kV1 January 2030
High voltage, 52 kV up to and including 145 kV and up to 50 kA, gas with a global warming potential of 1 or more1 January 2028
High voltage, above 145 kV or above 50 kA, gas with a global warming potential of 1 or more1 January 2032

Regulation (EU) 2024/573, Article 13(9). The prohibition attaches to putting equipment into operation, not to when it was made, which matters for unused surplus stock. Taking switchgear out of operation in the Union and putting it into operation at another Union site is not treated as putting into operation (Article 13(10)). The regulation provides derogations tied to the outcome of a procurement procedure (Article 13(11) and 13(12)). Whether a derogation applies to a project is a question for the project, not for this page.