Distribution transformers

1600 kVA distribution transformer

A 1600 kVA transformer delivers 2,309 A at 400 V on the low voltage side. At this rating it typically supplies large industrial loads, data halls, campuses and distribution centres.

1600 kVA at a glance

Rated power
1600 kVAthree phase
Rated current at 400 V
2,309 Acalculated
Rated current at 433 V
2,133 Acalculated
Primary current at 11 kV
84 Acalculated
EU load loss limit, liquid
≤ 12,000 WTier 2, class Ak
EU no load loss limit, liquid
≤ 1,080 WTier 2, Ao − 10 %
Dimensions and weight
with the quotationthey differ between units of the same rating
Outline drawing for orientation.Not a photograph of a specific unit. Arrangement, enclosure and dimensions depend on the unit offered.

Where a 1600 kVA unit is used

A 1600 kVA distribution transformer typically supplies large industrial loads, data halls, campuses and distribution centres. The rating is chosen from the connected load after diversity, the power factor and the starting behaviour of the largest motor, with headroom only for growth that is actually planned.

The low voltage current exceeds two thousand amperes, so the connection between transformer and board is normally busbar trunking, and the room layout is designed around it.

Common voltage configurations

PrimarySecondaryFrequencyPrimary currentSecondary currentContext
11 kV400 V50 Hz84 A2,309 A11 kV, listed as a standard voltage in IEC 60038
11 kV433 V50 Hz84 A2,133 A433 V secondary, documented in UK distribution specifications
10 kV400 V50 Hz92 A2,309 A10 kV networks, common in continental Europe
20 kV400 V50 Hz46 A2,309 A20 kV networks, common in continental Europe
22 kV400 V50 Hz42 A2,309 A22 kV networks
33 kV400 V50 Hz28 A2,309 A33 kV networks. The EU loss limit is corrected under Table I.3a
13.8 kV480 V60 Hz67 A1,925 A60 Hz networks with a 480 V secondary

Rated currents calculated as S / (√3 × U) for 1600 kVA, three phase. Configurations are the ones most often requested and are not a list of what is available. The network operator sets the primary voltage; IEC 60038 lists 230/400 V and 11 kV among standard voltages and notes that older 240/415 V systems remain in use.

What load a 1600 kVA transformer can carry, in kW

Load power factorReal power at full rating
0.801,280 kW
0.901,440 kW
0.951,520 kW
1.001,600 kW

Calculated as kW = kVA × power factor, at rated current and continuous duty. Diversity, planned growth, harmonic loads, ambient temperature, altitude and the largest motor start change the answer, which is why a load in kW does not fix the rating by itself. The sizing guide works through the method.

Construction and cooling

ConstructionCoolingTypical placement
Liquid immersed, mineral oilNatural oil and air, commonly ONANOutdoors, or a dedicated transformer room
Liquid immersed, esterNatural liquid and air, commonly KNANWhere fire point or biodegradability matters
Dry type, cast resinNatural air, with fans as an optionIndoors, including occupied buildings

Windings are copper or aluminium depending on the specification and the manufacturer's design. Insulation is the insulating liquid with solid insulation for liquid immersed units, and cast resin for dry type units.

Maximum losses on the EU market

ConstructionLoad losses PkNo load losses P0Basis
Liquid immersed≤ 12,000 W≤ 1,080 Wtable value, class Ak and Ao − 10 %
Dry type≤ 13,000 W≤ 1,980 Wtable value, class Ak and Ao − 10 %

Commission Regulation (EU) No 548/2014 as amended by (EU) 2019/1783, Annex I, Tables I.1 and I.2, Tier 2, applying from 1 July 2021. These limits apply to three phase medium power transformers with one winding at Um up to 24 kV and the other at Um up to 3.6 kV, and the regulation is still applied in Great Britain. A specific unit declares losses at or below them on its datasheet. Other markets set their own rules, which are confirmed for the destination in each quotation.

Indicative fault level at the low voltage terminals

SecondaryRated currentAt uk 6 %
400 V2,309 A38.5 kA
433 V2,133 A35.6 kA

Calculated as rated current divided by the short circuit impedance, assuming an infinite upstream source, so it is an upper bound for the transformer's contribution. The impedance of the unit offered is on its datasheet, and the design fault level is set by the designer's study, not by this table.

Standards commonly applied

StandardWhat it covers
IEC 60076-1Power transformers, general requirements
IEC 60076-11Dry type transformers, where the unit is cast resin
Regulation (EU) No 548/2014, as amendedMaximum losses on the EU market and in Great Britain
IEEE C57.12.00Liquid immersed transformers on North American specifications

Phase: three. Frequency: 50 Hz on IEC networks, 60 Hz on North American and some other networks.

Enclosure and protection options

ConstructionArrangementWhat decides it
Liquid immersedOutdoor tank with bushings, or with cable boxes on the high and low voltage sidesWhether connections are by overhead line, bare busbar or cable
Liquid immersedInside a compact substation enclosureWhether the transformer is bought alone or as part of a station
Dry typeNo enclosure, in a dedicated electrical roomWhether the room itself provides the protection
Dry typeVentilated housing to a stated IP ratingAccess by unauthorised people, dust and dripping water at the installed position

Degrees of protection are expressed with the IP code of IEC 60529. The rating required follows from the installed position, not from the transformer.

Accessories commonly specified

AccessoryConstructionPurpose
Off circuit tap changerBothAdjusts the ratio to the network voltage at the connection point
Temperature indication with alarm and trip contactsBothProtects the unit against overtemperature
Pressure relief deviceLiquid immersedRelieves internal pressure in a fault
Gas and oil actuated relayLiquid immersed with conservatorDetects internal faults and loss of liquid
Liquid level indicator and dehydrating breatherLiquid immersed with conservatorMonitors the liquid and keeps moisture out
Winding temperature sensors and relayDry typeAlarm and trip on winding temperature
Cooling fansDry typeIncreases output above the natural air rating
Cable boxesBothEncloses cable terminations
Rollers, lifting and haulage lugsBothHandling on arrival and positioning

Accessories vary by manufacturer and specification. Those included are listed in the quotation for the unit offered.

Dimensions and weight

Dimensions and weight are not published for a rating, because two units of the same rating can differ considerably. The construction, the loss level the core and windings are designed to, the cooling arrangement, the enclosure, the cable boxes and the conductor material all change the footprint and the mass.

They come from the outline drawing of the specific unit offered, which is provided with the quotation. That drawing is what the foundation, the room and the delivery are designed around, so it is worth having before those are fixed.

Documents normally requested

DocumentWhat it evidencesWhen it is normally provided
Technical datasheetRating, voltages, losses, impedance, dimensions and weight of the unit offeredWith the quotation
Outline drawingFootprint, lifting points and cable connection positionsWith the quotation or at order
Routine test reportThe individual unit's tests to its standardWith the delivered unit
Type test reportThe design has passed the type tests of its standardOn request, where a type test exists for the design
Rating plate detailsThe declared values carried on the unit itselfWith the delivered unit
Declaration of conformityConformity with the legislation of the destination marketWhere the destination market requires one
Operating and maintenance manualInstallation, operation and maintenance instructionsWith the delivered unit

Which documents apply depends on the destination market, the standard and the manufacturer. Documents are confirmed in the quotation for the specific unit offered.

What we need to quote a 1600 kVA transformer

01Rated power in kVA, or the connected load and the largest motor if the rating is not fixed yet
02Primary and secondary voltage, and the tapping range if the network operator sets one
03Phase, frequency and the vector group, or the earthing arrangement it has to suit
04Construction: liquid immersed or dry type, and whether oil is acceptable where the unit will stand
05Indoor or outdoor, ambient temperature, altitude and any corrosive or dusty exposure
06The standard and the loss requirement the destination market applies
07Quantity, destination and the date the equipment has to be on site
08Whether surplus or refurbished units are acceptable, or new only

Delivery and logistics

Distribution equipment is heavy, and a delivery date is only real once the site is ready for it. The dimensions and weight of the unit offered decide the vehicle, the lifting equipment and the route to the foundation, and they come from the manufacturer's drawing rather than from the rating.

Liquid immersed transformers are usually shipped filled, which affects transport rules and the handling on arrival. Anything crossing a border also carries customs documentation, and where the destination applies its own conformity or energy efficiency rules the paperwork has to match that market rather than the country of manufacture.

Lead times vary widely with rating, specification and manufacturer loading. We state a delivery basis in each quotation for the specific unit offered and do not publish a general lead time we cannot hold.

Common questions

What size of low voltage incomer does a 1600 kVA transformer need?

The rated current at 400 V is 2,309 A, and 2,133 A at 433 V. The incoming device is normally selected at the next standard rating above that current, commonly 2,500 A. The designer confirms the rating against the actual loading, the ambient and the discrimination study.

Does a 1600 kVA transformer have to meet the EU loss limits?

Where it is placed on the EU market, or in Great Britain, and falls within the regulation's scope, yes. For a three phase unit with one winding up to 24 kV Um and the other up to 3.6 kV Um, the liquid immersed limits at 1600 kVA are 12,000 W load losses and 1,080 W no load losses. A 36 kV Um primary and dual voltage windings are corrected under separate tables.

Related

Request a quote for this equipment

Send the rating, the voltage and the destination, or submit the specification, drawing or nameplate. Anything missing is raised before it reaches a supplier.